132CE PDFTitle:VENTILATION OF SCHEDULED PREMISES REGULATIONGazette Number:L.N. 320 of 1999
Section:6Heading:Annual inspection of dampers, filters and precipitatorsVersion Date:01/01/2000

(1) Every damper, filter and precipitator in any ventilating system that embodies the use of ducting or trunking in any scheduled premises shall be inspected at intervals not exceeding 12 months by a registered specialist contractor (ventilation works category).
(2) A registered specialist contractor (ventilation works category) who inspects any ventilating system under this section shall within 14 days of such inspection issue to the person on whose instructions the inspection was carried out a certificate and send a copy thereof to the Director of Fire Services.
(3) A certificate issued under subsection (2) shall state-

        (a) the address at which the inspection was carried out;
        (b) whether or not the dampers, filters and precipitators are in safe and efficient working order; and
        (c) the name and address of the registered specialist contractor (ventilation works category) who carried out the inspection.
(78 of 1999 s. 7)