369Y PDFTitle:MERCHANT SHIPPING (SAFETY) (FIRE PROTECTION) (SHIPS BUILT ON OR AFTER 1 SEPTEMBER 1984) REGULATIONSGazette Number:
Regulation:33Heading:Machinery spaces of Category AVersion Date:30/06/1997

(1) In every ship of Class VII of 500 tons or over there shall be provided for the protection of any machinery space of Category A at least one of the following fire extinguishing installations-

        (a) a fixed pressure water spraying system complying with the requirements of Schedule 8;
        (b) a fixed gas fire extinguishing system complying with the requirements of Schedule 10.
If the engine and boiler rooms are not entirely separated from each other by a bulkhead, or if fuel oil can drain from the boiler room into the engine room, the combined engine and boiler rooms shall for the purpose of this subregulation be regarded as a single space.
(2) In addition to the requirements of subregulation (1) there shall be provided-
        (a) in each boiler room one or more foam fire extinguishers each of at least 135 litres capacity or carbon dioxide fire extinguishers each of at least 45 kilograms capacity. The extinguishers shall be sited so as to be readily accessible in the event of fire and they shall be sufficient in number to enable foam or carbon dioxide to be directed on to any part of the boiler room and spaces containing any part of the oil fuel installation;
        (b) in each boiler room at least one portable foam applicator unit complying with the requirements of Schedule 6;
        (c) in each firing space and in each space which contains any part of any oil fuel installation, at least 2 portable fire extinguishers suitable for extinguishing oil fires, in addition to any which may be carried in compliance with paragraph (b);
        (d) in each firing space a receptacle containing 0.3 cubic metre of sand or other dry material suitable for extinguishing oil fires, together with a scoop for its distribution, or alternatively, an additional portable fire extinguisher suitable for extinguishing oil fires.
(3) In addition to the requirements of subregulation (1) there shall be provided in any such spaces containing internal combustion type machinery-
        (a) one or more foam fire extinguishers each of at least 45 litres capacity or carbon dioxide fire extinguishers of at least 16 kilograms capacity sufficient in number to enable foam or carbon dioxide to be directed on to any part of the fuel and lubricating oil pressure systems, gearing and other areas of high fire risk;
        (b) at least one portable foam applicator unit complying with the requirements of Schedule 6;
        (c) portable fire extinguishers suitable for extinguishing oil fires sufficient in number to ensure that at least one extinguisher is not more than 10 metres walking distance from any position within the space; provided that there shall be not less than 2 extinguishers.