Contents of Section

Chapter:

123B PDFTitle:Building (Construction) RegulationsGazette Number:L.N. 3 of 2011
Regulation:17Heading:Imposed loadsVersion Date:01/08/2011

(1) The imposed load on any building, street, building works or street works shall be the greatest applied load likely to arise from the intended use or purpose of the building, street, building works or street works (including forces exerted by the adjacent ground), but subject to this regulation-

    (a) the minimum imposed load on a building or street shall be-
        (i) the distributed load specified in column 3 of Table 1 applied uniformly on plan; or
        (ii) the concentrated load specified in column 4 of Table 1 applied on plan over any square with a 50 mm side (or over any square otherwise specified in that column) or the line load specified in that column, (L.N. 3 of 2011)
        (iii) (Repealed L.N. 3 of 2011)
        whichever shall produce the most adverse effect;
    (b) (Repealed L.N. 3 of 2011)
    (c) where the floor of a building is to support partitions but the position of the partitions is not indicated on the plan of the building, the weight of such partitions shall be regarded as imposed distributed load applied uniformly on plan and shall, in addition to other imposed loads, be- (L.N. 3 of 2011)
        (i) not less than 1/3 of the weight per metre length of the partitions uniformly distributed per square metre; and
        (ii) not less than 1 kPa if the floor is used for office purposes; (L.N. 3 of 2011)
    (d) where the floor of a building is to support any equipment, machinery or display item that will result in a greater imposed load than that specified in Table 1, the load of any of those items has to be considered in determining the imposed load on the floor. (L.N. 3 of 2011)
Table 1

Minimum Imposed Loads
1
2
3
4
Class
Use
Distributed load
in kPa to be
applied
uniformly on
plan
Concentrated
load in kN to be
applied on plan
over any square
with a 50 mm
side (unless
otherwise
specified in this
column), or line
load in kN per
metre length
1
Floors for—
    domestic use;

    dormitories;

    private sitting rooms, bedrooms and toilet rooms in hotels, motels and guesthouses;

    wards, bedrooms and toilet rooms in hospitals, nursing homes and residential care homes for elderly persons
2.0
2.0
2
Floors for—
    medical consulting or treatment rooms;

    hospital operating theatres and X-ray rooms
2.5
3.0
Floors for—
    laboratories;

    light workrooms with neither central power-driven machines nor storage;

    offices for general use;

    rooms for lightweight electrical and electronic installations
3.0
4.5
Floors for—
    banking halls;

    kitchens and laundries not in domestic buildings
4.0
4.5
3
Floors for—
    childcare centres and kindergartens
2.5
3.0
Floors for—
    billiard rooms and bowling alleys;

    classrooms, lecture rooms, tutorial rooms, computer rooms and reading rooms without book storage;

    dance practice rooms;

    leisure, recreational and amusement areas that cannot be used for assembly purposes
3.0
4.5
Floors for—
    assembly areas with fixed seating(1);

    chapels, churches and places of worship with fixed seating(1);

    restaurants, night-clubs, lounges, bars, canteens, fast food shops and dining rooms not in domestic premises
4.0
4.5
Floors for—
    art galleries and museums;

    grandstands;

    public halls;

    theatres and cinemas
5.0
4.5
Floors for—
    assembly areas without fixed seating(1);

    dance halls;

    footbridges between buildings;

    footpaths, terraces, plazas and areas used for pedestrian traffic;

    gymnasia;

    karaoke establishments and discotheques;

    refuge floors
5.0
4.5
Floors for—
    stages and television studios used as stages
7.5
9.0
4
Floors for—
    department stores, supermarkets, markets and shops for display and sale of merchandise
5.0
4.5
5
Floors for—
    library rooms with book storage (excluding library stack rooms);

    offices for storage and normal filing purposes
5.0
4.5
Floors for—
    (a) stack rooms in book stores and libraries

3.5 for each metre of storage height(2) but not less than 10.0
to be determined according to the weight of storage material, but not less than 9.0
    (b) old storage


5.0 for each metre of storage height(2) but not less than 15.0
to be determined according to the weight of storage material, but not less than 9.0
    (c) paper storage in printing plants

8.0 for each metre of storage height(2)
to be determined according to the weight of storage material, but not less than 9.0
    (d) battery rooms and uninterruptible power supply rooms
10.0 for each metre of storage height(2)to be determined according to the weight of storage material, but not less than 9.0
    (e) general storage other than those specified in (a), (b), (c) or (d) immediately above, including storage in warehouses
2.5 for each metre of storage height(2)to be determined according to the weight of storage material, but not less than 9.0
Floors for—
    plant rooms, boiler rooms, fan rooms, motor rooms and the like
7.5
9.0
Floors for—

    workshops, factories and other buildings or parts of buildings of similar category for industrial use—

    (a) for light weight loads
5.0
9.0
    (b) for medium weight loads
7.5
9.0
    (c) for heavy weight loads
10.0
9.0
    (d) for printing plants
12.5
9.0
6
Areas for—
    car parking, carriageways, floors, driveways and ramps used by vehicles—
    (a) for vehicles not exceeding 3000 kg gross weight
3.0
20.0 to be applied on plan over any square with a 200 mm side (instead of a 50 mm side)
    (b) for vehicles exceeding 3000 kg gross weight
to be determined according to recognized engineering principlesto be determined according to recognized engineering principles
7
Inaccessible roofs (where no access is provided except such access as may be necessary for maintenance work only) with a slope—
    (a) of or less than 5o
2.0
1.5
    (b) greater than 5o but less than 20o
0.75
1.5
    (c) of or greater than 20o but less than 40o
linear interpolation from 0.75 to 0 according to the slope
1.5
    (d) of or greater than 40o
0
1.5
Accessible roofs (where access is provided in addition to such access as may be necessary for maintenance work only) with a slope—
(a) of or less than 20o
2.0
1.5
(b) greater than 20o but less than 40olinear interpolation from 2.0 to 0 according to the slope
1.5

(c) of or greater than 40o
0
1.5
8
Floors for—
Utility platformssame as the floors to which they give access but not less than 4.0line load of 2.0 kN per metre length to be applied along the outer edge
Floors for—
Balconiessame as the floors to which they give access but not less than 3.0line load of 2.0 kN per metre length to be applied along the outer edge
Stairs, landings and corridorssame as the floors to which they give access but not less than 3.0 and not more than 5.0
4.5
Notes:

(1) Seating is regarded as fixed if the removal of the seating and the use of the relevant space for other purposes are unlikely to occur.

(2) Storage height (貯存高度) means the height of the space between the following: the floor, and a physical constraint to the height of storage formed by a ceiling, soffit of a floor, roof or other obstruction.
(L.N. 3 of 2011)

(1A) The greatest applied load mentioned in subregulation (1) must be derived from reliable data obtained from a source recognized by the Building Authority. (L.N. 3 of 2011)

(2) (a) Except as provided in paragraphs (b), (c), (d) and (e), in calculating the total imposed load on any column, pier, wall or foundation, the distributed imposed load on the roof and every floor carried thereby may be subject to the reductions specified in Table 2.
    (b) Where a single span of beam supports not less than 45 m2 of floor at any one level the distributed imposed load for the purpose only of determining the design of the beam may be subject to a reduction of 5% for each complete 45 m2 of that floor so supported but not more than 20% in all.
    (c) The reduction specified in paragraph (a) or (b), whichever is the greater, may be taken into account in calculating the total load on any column, pier, wall or foundation.
    (d) For factories and workshops designed for a distributed imposed load of 7.5 kPa or more the total imposed load shall not be reduced below that obtained if all the floors had been designed for a distributed imposed load of 7.5 kPa without the reduction specified in Table 2.
    (e) No reduction of the imposed loads shall be applied with respect to-
        (i) plant or machinery which is specifically allowed for; or
        (ii) floors of factories and workshops designed for a distributed imposed load of less than 7.5 kPa; or
        (iii) floors used by vehicles ; or (L.N. 3 of 2011)
        (iv) office areas used for storage and filing purposes; or
        (v) forces produced by dynamic effects; or (L.N. 3 of 2011)
        (vi) floors used for storage purposes; or (L.N. 3 of 2011)
        (vii) loads from partitions the positions of which are not indicated on the plan of the building. (L.N. 3 of 2011)
Table 2

Reductions of Total Distributed Imposed Loads
Number of floors
(including the roof) with
loads qualifying for
reduction carried by
the member
under consideration
Percentage reduction of total distributed imposed load
on all floors (including the roof) carried by the
member under consideration
Classes 1, 2, 3, 4 and
7 of Table 1
Workshops and factories under Class 5 of Table 1 with distributed imposed
load of not less than 7.5 kPa
1
0
0
2
5
10
3
10
20
4
15
5
20
6
25
25 maximum
7
30
8
35
over 8
40 maximum
(L.N. 3 of 2011)

(3) Protective barriers installed to restrict or control the movement of persons shall be designed to resist the minimum horizontal imposed loads specified in Table 3 when separately applied or the wind load (where applicable), whichever shall produce the more adverse effects.

Table 3

Minimum Horizontal Imposed Loads on Protective Barriers to Restrict
or Control Movement of Persons
Category
Line load to
be applied at
a height of 1.1
m above floor
level
Uniformly
distributed load
to be applied
on the infill
between floor
and top rail
Concentrated
load to be
applied on any
part of the infill
between floor
and top rail
kN/m
kPa
kN
Areas where congregation of people is not expected
0.75
1.0
0.5
Areas where people may congregate but overcrowding is not expected
1.5
1.5
1.5
Areas susceptible to overcrowding
3.0
1.5
1.5
(L.N. 3 of 2011)
    (4) Vehicle barriers for carriageways, floors, driveways and ramps used by vehicles must be designed to withstand the greatest impact force anticipated subject to the following requirements—
        (a) the minimum design impact force on vehicle barriers is to be [0.5 Mv2/ (δc + δb)] kN,

            where—

            M is the gross mass in kg of the heaviest vehicle to be accommodated,

            v is the velocity of the vehicle normal to the barrier in metre per second,

            δc is the deformation of the vehicle in mm, and

            δb is the deflection of the barrier in mm; and
        (b) the impact force is to be uniformly distributed over any length of 1.5 m and acting horizontally at the bumper height of the vehicle. (L.N. 3 of 2011)
        (5) (a) Forces produced by dynamic effects shall be considered as additional imposed loads in the design of buildings, streets, building works and street works.
          (b) The forces produced by dynamic effects in any workshop, factory or other building for industrial use may be determined on the basis of information about the particular building, but if not so determined shall be presumed-
              (i) for the purpose only of determining the design of slabs and beams, to be an additional vertical imposed load of 2.5 kPa; and
              (ii) for the purpose of determining the design of structural frames and foundations, to be an additional horizontal force (which may be assumed not to act together with the wind load) of 10% of the vertical imposed load specified in subparagraph (i) acting simultaneously on the N number of floors which will produce the most adverse effects, where N is a whole number not less than 0.2 times the total number of floors subject to dynamic effects.
        (Enacted 1990)